T & D - 17) Conductor Types Used For Overhead Lines


Conductor Types Used For Overhead Lines

Aluminium and its alloys conductor steel reinforced

The international standards covering most conductor types for overhead lines are IEC 61089(which supersedes IEC 207, 208, 209 and 210) and EN 50182 and 50183 (see Table 1).
For 36 kV transmission and above both aluminium conductor steel reinforced (ACSR) and all aluminium alloy conductor (AAAC) may be considered. Aluminium conductor alloy reinforced (ACAR) and all aluminium alloy conductors steel reinforced (AACSR) are less common than AAAC and all such conductors may be more expensive than ACSR.
Relevant national and international standards

StandardTitleComment
IEC 61089Round wire concentric lay overhead electrical stranded conductorsSupersedes IEC 207 (AAC), 208 (AAAC), 209 (ACSR) and 210 (AACSR)
EN 50182Conductor for overhead lines: round wire concentric lay stranded conductorSupersedes IEC 61089 for European use. BSEN 50182 identical
EN 50183Conductor for overhead lines: aluminium–magnesium–silicon alloy wires
BS 183Specification for general purpose galvanized steel wire strandFor earth wire
BS 7884Specification for copper and copper–cadmium conductors for overhead systems
Historically ACSR has been widely used because of its mechanical strength, the widespread manufacturing capacity and cost effectiveness.
For all but local distribution, copper-based overhead lines are more costlybecause of the copper conductor material costs. Copper (BS 7884 applies) has a very high corrosion resistance and is able to withstand desert conditions under sand blasting.
All aluminium conductors (AAC) are also employed at local distribution voltage levels.
From a materials point of view the choice between ACSR and AAAC is not so obvious and at larger conductor sizes the AAAC option becomes more attractive. AAAC can achieve significant strength/weight ratios and for some constructions gives smaller sag and/or lower tower heights. With regard to long-term creep or relaxation, ACSR with its steel core is considerably less likely to be affected.
Jointing does not impose insurmountable difficulties for either ACSR or AAAC types of conductor as long as normal conductor cleaning and general preparation are observed. AAAC is slightly easier to joint than ACSR.
Figure 1 illustrates typical strandings of ACSR. The conductor, with an outer layer of segmented strands, has a smooth surface and a slightly reduced diameter for the same electrical area.
Conductor arrangements for different CSR combinations
Figure 1 - Conductor arrangements for different CSR combinations
Historically there has been no standard nomenclature for overhead line conductors, although in some parts of the world code names have been used based on animal (ACSR – UK), bird (ACSR – North America), insect (AAAC – UK) or flower (AAAC – North America) names to represent certain conductor types.
Aluminium-based conductors have been referred to by their nominal aluminium area. Thus, ACSR with 54 Al strands surrounding seven steel strands, all strands of diameter d 3.18 mm, was designated 54/7/3.18; alu area 428.9 mm2, steel area 55.6 mm2 and described as having a nominal aluminium area of 400 mm2.
In France, the conductor total area of 485 mm2 is quoted and in Germany the aluminium and steel areas, 429/56, are quoted. In Canada and USA, the area is quoted in circular mils (1000 circular mils 0.507 mm2).
Within Europe standard EN50182 has coordinated these codes while permitting each country to retain the actual different conductor types via the National Normative Aspects (NNAs).
Table below explains the EN 50182 designation system.

Conductor designation system to EN50182:2001

  1. A designation system is used to identify stranded conductors made of aluminium with or without steel wires.
  2. Homogeneous aluminium conductors are designated ALx, where x identifies the type of aluminium. Homogeneous aluminium-clad steel conductors are designated yzSA where y represents the type of steel (Grade A or B, applicable to class 20SA only), and z represents the class of aluminium cladding (20, 21, 30 or 40).
  3. Composite aluminium/zinc coated steel conductors are designated ALxISTyz, where ALx identifies the external aluminium wires (envelope), and STyz identifies the steel core. In the designation of zinc coated steel wires, y represents the type of steel (Grades 1 to 6) and z represents the class of zinc coating (A to E).
  4. Composite aluminium/aluminium-clad steel conductors are designatedALxIyzSA, where ALx identifies the external aluminium wires (envelope), and yzSA identifies the steel core as in 2.
  5. Conductors are identified as follows:
    1. A code number giving the nominal area, rounded to an integer, of the aluminium or steel as appropriate;
    2. A designation identifying the type of wires constituting the conductor. For composite conductors the first description applies to the envelope and the second to the core.
The development of ‘Gap type’ heat-resistant conductors offers the possibility of higher conductor temperatures.
The design involves an extra high strength galvanized steel core, and heat-resistant aluminium alloy outer layers, separated by a gap filled with heat-resistant grease. To maintain the gap, the wires of the inner layer of the aluminium alloy are trapezoid shaped. Depending on the alloys used, temperatures of up to 210°C are possible, with a current carrying capacity of up to twice that of hard-drawn aluminium.
This offers particular value where projects involve upgrading existing circuits.

Tuesday, 28 May 2013

T & D - 5) What is the reason beyond three phase transmission?

As the need for increased transmission line capacity have forced power utility and owner to maximize power density in existing transmission corridors.  Many experienced have already been done on this, one way to get to this goal (increased capacity), is the use of more than three phases.
Theoretical and experimental studies have considered up to 36 phases systems. Up to 36 phases, the six-phase and twelve phase systems have been chosen the most attractive alternatives to replace for the three-phase systems.
Example of phase to phase voltages for multiple phase systems up to 36 phases are shown in below, comparing with the corresponding phase to ground voltages.
Comparison between phase to phase voltages with phases to ground for multiple phase systems in kV:
Phase to ground VoltagePhase to phase voltage
N36122436
8013880412114
133230133693523
1993451991035235
2895002891497550
43375043322411375

What are the key points of multiple phase lines?

  1. In six-phase systems, phase to phase voltages are equal to phase to ground voltages.
  2. For the orders higher than six, phase to phase voltages between adjacent phases are lower than phase to ground voltages. This is the reason that always in multiple phase systems, the phase to ground voltages are taken as reference.
  3. Whereas in three phase systems phase to phase voltages are always equal, phase to phase voltages in multiple phase systems depend on the selected conductor combination.

 Properties of multiple phase systems

Comparing with three phase system, we get the following characteristics of multiple phase system.
  1. Lower voltage for the same power can be transmitted.
  2. Lower phase to phase and phase to ground clearances and shorter towers with narrow right of way
  3. Lower phase to phase spacing
  4. Lower voltage gradients, resulting smaller conductor size to used.
  5. With increasing number of phases, the probability of flashovers’ between phases increases. Therefore special attention must be paid to the design of insulation
  6. Power transmission with more than three phases, for example six-phases, requires corresponding transformers and circuit breakers, switchgear and bus bars for six poles as well, what is more expensive and results in difficult protection (relaying) when interconnected with three phase lines. Therefore, the use of multiple phase transmission is presently restricted to some few lines.