Low voltage switchgear - Power distribution |
Continued from Types of neutral earthing in power distribution (part 1)
3. Resistance earthed systems
Resistance
grounding has been used in three-phase industrial applications for many
years and it resolves many of the problems associated with solidly
grounded and ungrounded systems. Resistance Grounding Systems limits the
phase-to-ground fault currents.
The main reasons for limiting the phase to ground fault current by resistance grounding are:
- To reduce burning and melting effects in faulted electrical equipment like switchgear, transformers, cables, and rotating machines.
- To reduce mechanical stresses in circuits/Equipments carrying fault currents.
- To reduce electrical-shock hazards to personnel caused by stray ground fault.
- To reduce the arc blast or flash hazard.
- To reduce the momentary line-voltage dip.
- To secure control of the transient over-voltages while at the same time.
- To improve the detection of the earth fault in a power system.
Grounding Resistors are generally connected between ground and neutral of transformers, generators and grounding transformers to limit maximum fault current as per Ohms Law to a value which will not damage the equipment
in the power system and allow sufficient flow of fault current to
detect and operate Earth protective relays to clear the fault. Although
it is possible to limit fault currents with high resistance Neutral
grounding Resistors, earth short circuit currents can be extremely
reduced.
As a result of this fact, protection devices may not sense the fault.
Therefore,
it is the most common application to limit single phase fault currents
with low resistance Neutral Grounding Resistors to approximately rated
current of transformer and / or generator.
In addition, limiting
fault currents to predetermined maximum values permits the designer to
selectively coordinate the operation of protective devices, which
minimizes system disruption and allows for quick location of the fault.
There are two categories of resistance grounding:
- Low resistance Grounding
- High resistance Grounding
Ground fault current flowing through either type of resistor when a single phase faults to ground will increase the phase-to-ground voltage of the remaining two phases. As a result, conductor insulation and surge arrestor ratings must be based on line-to-line voltage.
This temporary increase in phase-to-ground voltage should also be
considered when selecting two and three pole breakers installed on
resistance grounded low voltage systems.
The increase in
phase-to-ground voltage associated with ground fault currents also
precludes the connection of line-to-neutral loads directly to the
system. If line-to neutral loads (such as 277V lighting) are present,
they must be served by a solidly grounded system. This can be achieved
with an isolation transformer that has a three-phase delta primary and a
three-phase, four-wire, wye secondary.
Neither
of these grounding systems (low or high resistance) reduces arc-flash
hazards associated with phase-to-phase faults, but both systems
significantly reduce or essentially eliminate the arc-flash hazards
associated with phase-to-ground faults. Both types of grounding systems
limit mechanical stresses and reduce thermal damage to electrical
equipment, circuits, and apparatus carrying faulted current.
The
difference between Low Resistance Grounding and High Resistance
Grounding is a matter of perception and, therefore, is not well defined.
Generally speaking high-resistance grounding refers to a system in
which the NGR let-through current is less than 50 to 100 A.Low resistance grounding indicates that NGR current would be above 100 A.
A
better distinction between the two levels might be alarm only and
tripping. An alarm-only system continues to operate with a single ground
fault on the system for an unspecified amount of time. In a tripping
system a ground fault is automatically removed by protective relaying
and circuit interrupting devices. Alarm-only systems usually limit NGR
current to 10 A or less.
Rating of The Neutral grounding resistor:
- Voltage: Line-to-neutral voltage of the system to which it is connected.
- Initial Current: The initial current which will flow through the resistor with rated voltage applied.
- Time: The “on time” for which the resistor can operate without exceeding the allowable temperature rise.
A. Low Resistance Grounded
Low
Resistance Grounding is used for large electrical systems where there
is a high investment in capital equipment or prolonged loss of service
of equipment has a significant economic impact and it is not commonly
used in low voltage systems because the limited ground fault current is
too low to reliably operate breaker trip units or fuses. This makes
system selectivity hard to achieve. Moreover, low resistance grounded
systems are not suitable for 4-wire loads and hence have not been used
in commercial market applications.
A resistor is connected from the system neutral point to ground and generally sized to permit only 200A to 1200 amps
of ground fault current to flow. Enough current must flow such that
protective devices can detect the faulted circuit and trip it off-line
but not so much current as to create major damage at the fault point.
Low resistance grounded |
Since
the grounding impedance is in the form of resistance, any transient
over voltages are quickly damped out and the whole transient overvoltage
phenomena is no longer applicable. Although theoretically possible to
be applied in low voltage systems (e.g. 480V),significant amount of the
system voltage dropped across the grounding resistor, there is not
enough voltage across the arc forcing current to flow, for the fault to
be reliably detected.
For this reason low resistance grounding is not used for low voltage systems (under 1000 volts line to-line).
Advantages
- Limits phase-to-ground currents to 200-400A.
- Reduces arcing current and, to some extent, limits arc-flash hazards associated with phase-to-ground arcing current conditions only.
- May limit the mechanical damage and thermal damage to shorted transformer and rotating machinery windings.
Disadvantages:
- Does not prevent operation of over current devices.
- Does not require a ground fault detection system.
- May be utilized on medium or high voltage systems.
- Conductor insulation and surge arrestors must be rated based on the line to-line voltage. Phase-to-neutral loads must be served through an isolation transformer.
- Used: Up to 400 amps for 10 sec are commonly found on medium voltage systems.
B. High Resistance Grounded
High resistance grounding is almost identical to low resistance grounding except that the ground fault current magnitude is typically limited to 10 amperes or less. High resistance grounding accomplishes two things.
The first is that the ground fault current magnitude is sufficiently low enough such
that no appreciable damage is done at the fault point. This means that
the faulted circuit need not be tripped off-line when the fault first
occurs. Means that once a fault does occur, we do not know where the
fault is located. In this respect, it performs just like an ungrounded
system.
The second point is it can control the transient overvoltage phenomenon present on ungrounded systems if engineered properly.
Under
earth fault conditions, the resistance must dominate over the system
charging capacitance but not to the point of permitting excessive
current to flow and thereby excluding continuous operation.
High resistance grounded |
High
Resistance Grounding (HRG) systems limit the fault current when one
phase of the system shorts or arcs to ground, but at lower levels than
low resistance systems.
In the event that a ground fault condition exists, the HRG typically limits the current to 5-10A.
HRG’s
are continuous current rated, so the description of a particular unit
does not include a time rating. Unlike NGR’s, ground fault current
flowing through a HRG is usually not of significant magnitude to result
in the operation of an over current device. Since the ground fault
current is not interrupted, a ground fault detection system must be
installed.
These systems include a bypass contactor tapped across a
portion of the resistor that pulses (periodically opens and closes).
When the contactor is open, ground fault current flows through the
entire resistor. When the contactor is closed a portion of the resistor
is bypassed resulting in slightly lower resistance and slightly higher
ground fault current.
To avoid transient over-voltages, an HRG resistor must be sized so that the amount of ground fault current
the unit will allow to flow exceeds the electrical system’s charging
current. As a rule of thumb, charging current is estimated at 1A per
2000KVA of system capacity for low voltage systems and 2A per 2000KVA of
system capacity at 4.16kV.
These estimated charging currents
increase if surge suppressors are present. Each set of suppressors
installed on a low voltage system results in approximately 0.5A of
additional charging current and each set of suppressors installed on a
4.16kV system adds 1.5A of additional charging current.
A system
with 3000KVA of capacity at 480 volts would have an estimated charging
current of 1.5A.Add one set of surge suppressors and the total charging
current increases by 0.5A to 2.0A. A standard 5A resistor could be used
on this system. Most resistor manufacturers publish detailed estimation
tables that can be used to more closely estimate an electrical system’s
charging current.
Advantages
- Enables high impedance fault detection in systems with weak capacitive connection to earth
- Some phase-to-earth faults are self-cleared.
- The neutral point resistance can be chosen to limit the possible over voltage transients to 2.5 times the fundamental frequency maximum voltage.
- Limits phase-to-ground currents to 5-10A.
- Reduces arcing current and essentially eliminates arc-flash hazards associated with phase-to-ground arcing current conditions only.
- Will eliminate the mechanical damage and may limit thermal damage to shorted transformer and rotating machinery windings.
- Prevents operation of over current devices until the fault can be located (when only one phase faults to ground).
- May be utilized on low voltage systems or medium voltage systems up to 5kV. IEEE Standard 141-1993 states that “high resistance grounding should be restricted to 5kV class or lower systems with charging currents of about 5.5A or less and should not be attempted on 15kV systems, unless proper grounding relaying is employed”.
- Conductor insulation and surge arrestors must be rated based on the line to-line voltage. Phase-to-neutral loads must be served through an isolation transformer.
Disadvantages
- Generates extensive earth fault currents when combined with strong or moderate capacitive connection to earth Cost involved.
- Requires a ground fault detection system to notify the facility engineer that a ground fault condition has occurred.
4. Resonant earthed system
Adding
inductive reactance from the system neutral point to ground is an easy
method of limiting the available ground fault from something near the
maximum 3 phase short circuit capacity (thousands of amperes) to a
relatively low value (200 to 800 amperes).
To limit the reactive
part of the earth fault current in a power system a neutral point
reactor can be connected between the transformer neutral and the station
earthing system.
A system in which at least one of the neutrals is connected to earth through an
- Inductive reactance.
- Petersen coil / Arc Suppression Coil / Earth Fault Neutralizer.
The
current generated by the reactance during an earth fault approximately
compensates the capacitive component of the single phase earth fault
current, is called a resonant earthed system.
The system is hardly
ever exactly tuned, i.e. the reactive current does not exactly equal
the capacitive earth fault current of the system.
A system in
which the inductive current is slightly larger than the capacitive earth
fault current is over compensated. A system in which the induced earth
fault current is slightly smaller than the capacitive earth fault
current is under compensated.
However,
experience indicated that this inductive reactance to ground resonates
with the system shunt capacitance to ground under arcing ground fault
conditions and creates very high transient over voltages on the system.
To control the transient over voltages, the design must permit at least
60% of the 3 phase short circuit current to flow underground fault
conditions.
Example
– A 6000 amp grounding reactor for a system having 10,000 amps 3 phase
short circuit capacity available. Due to the high magnitude of ground
fault current required to control transient over voltages, inductance
grounding is rarely used within industry.
Petersen Coils
A
Petersen Coil is connected between the neutral point of the system and
earth, and is rated so that the capacitive current in the earth fault is compensated by an inductive current passed by the Petersen Coil.
A small residual current will remain, but this is so small that any arc
between the faulted phase and earth will not be maintained and the
fault will extinguish. Minor earth faults such as a broken pin
insulator, could be held on the system without the supply being
interrupted. Transient faults would not result in supply interruptions.
Although
the standard ‘Peterson coil’ does not compensate the entire earth fault
current in a network due to the presence of resistive losses in the
lines and coil, it is now possible to apply ‘residual current
compensation’ by injecting an additional 180° out of phase current into
the neutral via the Peterson coil. The fault current is thereby reduced
to practically zero. Such systems are known as ‘Resonant earthing with
residual compensation’, and can be considered as a special case of
reactive earthing.
Resonant earthing can reduce EPR to a safe
level. This is because the Petersen coil can often effectively act as a
high impedance NER, which will substantially reduce any earth fault
currents, and hence also any corresponding EPR hazards (e.g. touch
voltages, step voltages and transferred voltages, including any EPR
hazards impressed onto nearby telecommunication networks).
Advantages
- Small reactive earth fault current independent of the phase to earth capacitance of the system.
- Enables high impedance fault detection.
Disadvantages
- Risk of extensive active earth fault losses.
- High costs associated.
5. Earthing Transformers
For
cases where there is no neutral point available for Neutral Earthing
(e.g. for a delta winding), an earthing transformer may be used to
provide a return path for single phase fault currents.
In
such cases the impedance of the earthing transformer may be sufficient
to act as effective earthing impedance. Additional impedance can be
added in series if required. A special ‘zig-zag’ transformer is
sometimes used for earthing delta windings to provide a low
zero-sequence impedance and high positive and negative sequence
impedance to fault currents.
Conclusion
Resistance
Grounding Systems have many advantages over solidly grounded systems
including arc-flash hazard reduction, limiting mechanical and thermal
damage associated with faults, and controlling transient over voltages.
High
resistance grounding systems may also be employed to maintain service
continuity and assist with locating the source of a fault.
When
designing a system with resistors, the design/consulting engineer must
consider the specific requirements for conductor insulation ratings,
surge arrestor ratings, breaker single-pole duty ratings, and method of
serving phase-to-neutral loads.
Comparison of Neutral Earthing System
Condition | Ungrounded | Solid Grounded | Low Resistance Grounded | High Resistance Grounded | Reactance Grounding |
Immunity to Transient Over voltages | Worse | Good | Good | Best | Best |
73% Increase in Voltage Stress Under Line-to-Ground Fault Condition | Poor | Best | Good | Poor | |
Equipment Protected | Worse | Poor | Better | Best | Best |
Safety to Personnel | Worse | Better | Good | Best | Best |
Service Reliability | Worse | Good | Better | Best | Best |
Maintenance Cost | Worse | Good | Better | Best | Best |
Ease of Locating First Ground Fault | Worse | Good | Better | Best | Best |
Permits Designer to Coordinate Protective Devices | Not Possible | Good | Better | Best | Best |
Reduction in Frequency of Faults | Worse | Better | Good | Best | Best |
Lighting Arrestor | Ungroundedneutral type | Grounded-neutral type | Ungroundedneutral type | Ungroundedneutral type | Ungroundedneutral type |
Current for phase-to ground fault in percent of three-phase fault current | Less than 1% | Varies, may be 100% or greater | 5 to 20% | Less than 1% | 5 to 25% |
No comments:
Post a Comment